Estimate how much power is saved if the voltage is stepped up from 150 VV to 1500 VV and then down again, rather than simply transmitting at
Question
Estimate how much power is saved if the voltage is stepped up from 150 VV to 1500 VV and then down again, rather than simply transmitting at 150 VV . Assume the transformers are each 99%% efficient. Express your ans
in progress
0
Physics
4 years
2021-08-27T06:39:32+00:00
2021-08-27T06:39:32+00:00 1 Answers
32 views
0
Answers ( )
The question is incomplete! The complete question along with answer and explanation is provided below.
Question:
Suppose 79 kW is to arrive at a town over two 0.115 Ω lines. Estimate how much power is saved if the voltage is stepped up from 150 V to 1500 V and then down again, rather than simply transmitting at 150 V. Assume the transformers are each 99%% efficient. Express your ans up to two decimal points.
Answer:
Power saved = 30772.58 W or 30.77 kW
Explanation:
Since the power loss depends upon current, we need to find the current at each voltage level.
Current at 150 V:
I = P/V = 79,000/150 = 526.67 A
Current at 1500 V:
Considering transformer efficiency of 99%
79,000/0.99 = 79797.97 W
I = P/V = 79,797.97/1500 = 53.19 A
Power loss at 150 V:
P = I²R = (526.67)²*0.115 = 31898.84 W
Power loss at 1500 V:
Here we have to consider both of the losses, due to the transmission line and due to transformer itself
P = I²R = (53.19)²*0.115 = 325.35 W
So the total power at the sending end would be
Receiving end power + losses
79,000 + 325.35 = 79,325 W
Power at the input of the transformer is
79,325/0.99 = 80126.26
Power lost in the transformer is
80,126.26 – 79,000 = 1126.26 W
So the power that can be saved by stepping up the voltage from 150 to 1500 V is
Power saved = 31898.84 – 1126.26
Power saved = 30772.58 W
Power saved = 30.77 kW